Series34 MM Changing the Target

ADJUSTING THE TARGET (FOR SERIES 3400
TYPE INDICATORS):(For assemblies made after 8/12)
NOTE:
For an “open left” valve the “OPEN” sign should be mounted
above the “SHUT” sign. (Fig. 2B) For an “open right” valve the
“SHUT” sign should be mounted above the “OPEN” sign.
(Fig. 2C).
1. With a 3/8”, (10mm) allen wrench, remove the four Bonnet
Bolts (F216) attaching the Bonnet (F337), to the Head/Upper
Barrel Assembly (F327). (See Fig. 2A).
2. Pull the Bonnet and Target Assembly away from the Head/
Upper Barrel.
3. If the Post Indicator is to be mounted on an open left valve,
the “OPEN” Plate (F321) remains in the top position of the
Target (F318). (See Fig. 2B).

4. To configure for “open right” remove the Plate Attachment
Screws (F322), and Plate Nuts (F320) with a flat bladed
screwdriver and 7/16”,(11mm) wrench. Switch the locations
of the “OPEN” and “SHUT” Plates. The “SHUT” Plate F319,
should be mounted on top. (See Fig. 2C).
5. Re-attach the associated hardware. Ensure that the “OPEN”
Plate is in the correct location for the size of valve that the
Post Indicator is being mounted on.
NOTE: Each set of dimples in the target is marked for the
correct valve size (4″ through (12-16″)). The Target
Spacer (F323) should always be mounted on the
Attachment Bolts that attach the “OPEN” plate.
(See Fig. 3, on page 5)
6. Lift the re-assembled post indicator Bonnet/Target Assembly
onto the Head/Upper Barrel Assembly. Make sure the upper
stem rod slides into the lower stem rod.
7. Install and tighten the four Bonnet Bolts (F216) attaching the
Bonnet (F337) to the Head/Upper Barrel Upper Barrel
Assembly (F327) .

Click The Image to Read Up more on Our Series 34 Maintenance Manual

Categories
Uncategorized

Series 67 In-Depth

Features

  • Stainless steel upper stem – standard
  • Breakable flange and stem coupling – standard
  • EPDM encapsulated one-piece main valve – standard
  • Fusion Bonded Epoxy Coated Shoe with integral foot for easy installation – standard
  • Rated to 250 psi working pressure – standard
  • All ductile-iron construction

 

 

 

  • All internal working parts are removable from the top for easy maintenance
  • Any bury depth available
  • Self draining to prevent freezing
  • Bronze drain ring and main valve seat
  • Optional stainless steel lower stem
  • Open left or open right
Categories
Uncategorized

Product Traceability

PRODUCT TRACEABILITY

Our Hydrants, Gate Valves, Butterfly Valves, and Post Indictors all have a unique serial number engraved on them. This serial number has a variety of information attached to it, like who built the product, material, testing results, and a list of other information. This serial number is also helpful when ordering replacement parts as well as providing information to the customer. These serial number are located on different parts of our products. To get a better understanding of our product traceability check out the informational video below.